Abstract
Fault vulnerability and protection issues are major challenge in realising multi-terminal HVDC transmission system, also termed HVDC grids. This paper presents a novel time domain and transient based protection technique for application to HVDC grids. The technique utilises the energy of the forward and backward travelling waves produced by a fault to distinguish between internal and external faults. For an internal fault, the calculated forward or backward travelling wave energy for a pre-set time duration following the occurrence of a fault must exceed a predetermined setting otherwise the fault is external. This characteristic is largely due to the DC inductor located at the cable ends, as per HVDC breakers or fault current limiters, which provides attenuation for the high frequency transients resulting from an external fault. The ratio between the forward travelling wave energy and the backward travelling wave energy provides directional comparison. For a forward directional fault with respect to a local relay, this ratio must be less than unity whereas the ratio is greater than unity for a reverse directional fault. The simulation results presented based on full scale Modular Multilevel Converter Based HVDC grid shows the suitability of the proposed technique. An advantage of this technique is that it is non-unit based and as such no communication delay is incurred. Furthermore, it is simple as it does not require complex mathematical/DSP technique; and as such can be easily implemented at each independent relay since it will require minimal hardware resources hence reduces cost.
Original language | English |
---|---|
Pages (from-to) | 300-314 |
Number of pages | 15 |
Journal | Sustainable Energy, Grids and Networks |
Volume | 16 |
Early online date | 3 Oct 2018 |
DOIs | |
Publication status | Published - Dec 2018 |
Bibliographical note
NOTICE: this is the author’s version of a work that was accepted for publication in Sustainable Energy, Grids and Networks]. Changes resulting from the publishing process, such as peer review, editing, corrections, structural formatting, and other quality control mechanisms may not be reflected in this document. Changes may have been made to this work since it was submitted for publication. A definitive version was subsequently published in Sustainable Energy, Grids and Networks, [16], (2018] DOI: 10.1016/j.segan.2018.09.003© 2017, Elsevier. Licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International http://creativecommons.org/licenses/by-nc-nd/4.0/
Copyright © and Moral Rights are retained by the author(s) and/ or other copyright owners. A copy can be downloaded for personal non-commercial research or study, without prior permission or charge. This item cannot be reproduced or quoted extensively from without first obtaining permission in writing from the copyright holder(s). The content must not be changed in any way or sold commercially in any format or medium without the formal permission of the copyright holders.
Keywords
- HVDC grid protection
- Transient based protection
- Travelling wave energy
Fingerprint
Dive into the research topics of 'A novel time domain protection technique for multi-terminal HVDC networks utilising travelling wave energy'. Together they form a unique fingerprint.Profiles
-
Monday Ikhide
- School of Energy, Construction and Environment - Assistant Professor (Academic)
Person: Teaching and Research